Description:
With the continuous development, the switching station in the integrated and modular way has emerged. XGW-12 type Intelligent Box Switching Station integrates the detection, protection, control and measurement of power equipment under normal and accident conditions with the use of modern sensor technology, communication technology, computer network technology, greatly improving the operational reliability of urban power grids.
Features:
u Less floor space and shorter construction period.
u Integration of primary and secondary systems as well as modularized assembly.
u Multiple options and flexible configuration.
u Perfect Five-protection and Interlocking system. Safe and reliable, easy to repair.
Using environment:
u Temperature: Min -40℃~Max+40℃;
u Relative humidity: Daily average ≦95%; Monthly average≦90%;
u Altitude: ≦1000m;
u Shock level: Horizontal acceleration 0.4m/s2,Vertical acceleration 0.15m/s2;
u Installation location: The place with no severe impact, serious pollution and chemical corrosion, no conductive dust and explosion risk.
When the conditions of use exceed the above range, the user shall negotiate with us to determine the allowable range or take corresponding supplementary technical measures.
Technical Parameters:
NO | Item | Unit | Standard value | |
1 | Rated voltage | KV | 12 | |
2 | Insulating medium |
| SF6 | |
3 | Type of Arc-extinguishing chamber |
| SF6 | |
4 | Rated frequency | HZ | 50 | |
5 | Rated current | A | 630 | |
6 | Temperature rise test current |
| 1.1lr | |
7 | 1min Power frequency withstand voltage (phrase to ground) | KV | 42 | |
8 | Rated lightning impulse withstand voltage (1.2/50Qs)(phrase to ground)(peak) | KV | 75 | |
9 | Rated short-circuit breaking current | KA | 20 | |
10 | Rated short-circuit closing current(peak) | KA | 50 | |
11 | Rated short-time withstand current and duration | KA/S | 20/4 | |
12 | Stable peak withstand current | KA | 50 | |
13 | Arcing duration | S | ≥0.5 | |
14 | Number of breaks under rated active load conditions | Time | ≥200 | |
15 | Auxiliary and control loop short-duration power frequency withstand voltage | KV | 2 | |
16 | Power supply | Control loop(independent) | V | DC 48 |
Auxiliary loop | V | DC 48/AC 220 | ||
Energy storage loop (independent) | V | DC 48/AC 220 | ||
17 | Service life | Year | ≥40 | |
18 | IP grade | Cabinet shell |
| IP40 |
Compartment room |
| IP2X | ||
19 | Cabinet shell |
| ≤0.1% | |
20 | Compartment room |
| Electric with manual operation function |